Model | Description |
ES2030SV-1 | (1 input and 6 outputs). For 1 or 2 columns with with max. 6 (8) electric valves total. Power in / out : 24/24, 115/115 or 230/230 VAC |
ES2030SV-2 | (1 input and 6 outputs). For 1 or 2 columns with with max. 6 (8) electric valves total. Power in / out : 115/24 or 230/24 VAC |
ES2030SV-3 | (2 inputs and 8 outputs). For 1 or 2 columns with with max. 6 (8) electric valves total. Power in / out : 24/24, 115/115 or 230/230 VAC |
ES2030SV-4 | (2 inputs and 8 outputs). For 1 or 2 columns with with max. 6 (8) electric valves total. Power in / out : 115/24 or 230/24 VAC |
ES2030SV-5 | (6 inputs and 15 outputs). For 1 or 2 columns with with max. 15 electric valves. Power in / out : 24/24, 115/115 or 230/230 VAC |
ES2030SV-6 | (6 inputs and 15 outputs). For 1 or 2 columns with with max. 15 electric valves. Power in / out : 115/24 or 230/24 VAC |
- User operated programming using double row of illuminated LCD display
- Display text in English, French, German, Italian, Spanish or Dutch
- Simple control utilising easy to follow symbols
- Built-in audio signal for 7 programmed signal indicators
- Adaption to user specific requirements by means of options programmable on site
- Simple operation by means of a few clear operating symbols
- Can be used for various sizes of plant
- Capacity values programmable from 1 to 65535 m3 E or from 0.01 to 9999.99 m3
- Regeneration/rinsing activation by time interval, flow, external switching, real time clock or manual control
- Time delayed regeneration/rinsing
- Control of quantity dependent flushing
- Extensive status report facility using information button
- Flush control
- regeneration/rinsing time
- extra program
- filter capacity
- total quantity of treated water
- current input and outputs status
- software version
- start time interval
- time delayed regeneration/rinsing
- service telephone number
- input and output programming
- Input of service telephone number
- 1 programmable input: water meter, regeneration/rinsing stop, regeneration/rinsing start or regeneration/rinsing agent monitoring
- 1 optional programmable input(IF circuit board) for water meter, regeneration/rinsing stop, regeneration/rinsing start or regeneration/rinsing agent monitoring
- Inputs programmable active open or closed
- 2 optional programmable outputs: extra program, regeneration/rinsing procedure, take-off impulse, signalling or flushing. Output relay programmable active under current or not under current
- Secure from power failure as all data is stored long-term without battery
- Real time clock with battery back-up
- SD Card holder for software updates
- Efficient micro controller with watchdog, illegal operation code and cycle monitoring
- Safeguarded from EMC by galvanic separation between micro controller and in- and output circuits and also by additional interference suppression filter
- Available for wall-mounting